Go to Editorial ManagerIn this paper, energy and exergy concepts have been carried out on one of the largest gas turbine power plants in Iraq (Rumaila-Basra). Both ISO operating conditions as well as actual operating data recorded for one month in hot season are considered. Results indicate that a lot of heat energy accompanied with remarkable exergy is discharged to the atmosphere. Also, it is found that the combustion chamber has the largest exergy destruction among the plant components. Possibility of cooling the intake air drawn by the compressor and its effects on the plant performance is studied. The required cooling load is found to be in the range 3379 T.R for part load operation to 4723.3 T.R for full load operation.
In this work, both energy and exergy analyses have been carried out on General Electric (GE) gas turbine unit found in Khor Al-Zubair gas turbine power plant located in Basra, Iraq. The analysis covers the ISO (international standards organization) operating conditions in addition to actual operating data recorded for one month in hot season July 2016. The feasibility of adopting a vapor compression cycle (VCC) for cooling the intake air is evaluated. Generally, the study reveals an obvious drop off for most plant performance characteristics while operating during the hot season. Energy and exergy analyses show that adopting the vapor compression cycle to enhance Khor Al-Zubair GE unit could improve the power output by 20% and 27% in case of part-load and full-load conditions respectively. Both of first and second law efficiencies could be improved by 3.5% at part- load and 9% at full load. The expected cooling load needed for the unit is in the range of 2697 to 3024.5 TR according to part- load and full-load operation respectively. Only total irreversibility of the unit is expected to increase in case of adopting VCC and this will not impair the improvement in second law efficiency of the unit. Among the unit components, combustion chamber has the largest computed irreversibility. Further improvement is recommended by utilizing the released heat energy to the atmosphere, which is characterized by significant work potential.
In This paper, an experimental study was carried out on a dual channel with perforating “V” corrugated absorber plate of solar air collector which the air flows both in upper channel and lower channel of the absorber plate for increasing heat transfer coefficient and improving thermal performance. The results of experimental procedures for dual channel with perforating “V” corrugated absorber plate of solar collector were compared with the flat plate dual channel of solar collector. Experimental calculations had been performed under Baghdad (33.34° North latitude, 44.4° East longitude) climatic conditions at different values of mass flow rates 0.021 kg/s, 0.027 kg/s and 0.32 kg/s. The results showed that the dual channel with perforating “V” corrugated absorber plate of solar collector is found to perform more efficiently than the flat plate dual channel of solar collector with increased 39% in thermal efficiency. Then, it showed that the efficiency increases with increasing mass flow rates. Also, it showed that the heat removal factor of the dual channel with perforating “V” corrugated absorber plate of solar collector is 36% more than the flat plate dual channel of solar collector. At the last part of the study, the exergy relations were derived for both collectors. The results of this part showed that the flat plate dual channel of solar collector is having largest irreversibility (exergy loss) and the dual channel with perforating “V” corrugated absorber plate of solar collector is having a greatest exergetic efficiency.